Actively exploited vulnerability / CVE-2026-58115
Siemens SIMATIC IoT2050 Advanced: attackers can take full control of the device
When Node-RED is installed on the device, its web interface does not require a login, so anyone who can reach it over the network can run any code on the device with full privileges. For a business, this can mean disrupted or manipulated production processes and a foothold into the rest of the network. This vulnerability is on the list of vulnerabilities used in real attacks kept by ENISA, the EU cybersecurity agency.
- Identifier
- CVE-2026-58115 · EUVD-2026-56119
- Severity
- Critical (10/10)
- On the ENISA list (EU)
- yes
- Probability of exploitation (EPSS)
- 1.0% (FIRST's estimate for the next 30 days)
Does it concern you?
The SIMATIC IoT2050 Advanced is a small industrial computer from Siemens used to connect machines and sensors to networks and monitoring software. It is typically found in factories, production sites and technical installations.
Affected are devices with order number 6ES7647-0BA00-1YA2 running Industrial OS with Node-RED installed, in all versions before V4.3.4.1. The technician or integrator who set up the device can check the system version; if you are unsure who manages it, ask your automation supplier.
What to do
Update the system to version V4.3.4.1 or later. Until then, have your technician make sure the Node-RED interface cannot be reached from networks that do not need it, and follow Siemens' guidance.
The official description
The text below is the description from the public database.
A vulnerability has been identified in SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All versions < V4.3.4.1 running Industrial OS with Node-RED installed). Affected devices do not enforce authentication on the Node-RED HTTP interface, allowing unauthenticated access to programming nodes that are capable of executing system commands on the server. This could allow an unauthenticated remote attacker to create malicious flows through the HTTP interface in order to execute arbitrary code on the underlying server with maximum privileges.
Sources
Data from the public CVE and NVD databases, the CISA KEV and ENISA EU KEV lists and FIRST's EPSS score. The explanations are ours, written from that data. Last updated: 29 November 2026.